Dobro dosli ..............logo cipivan007@gmail.com . . . . .

 

 

 

Bimetali JRS CIP JRS2 3UA serije

 

 

 

 

JRS2(3UA) Series Thermal Relay

JRS2-12.5/Z
JRS2-25/Z
JRS2-32/Z
JRS2-45/Z
JRS2-63/Z
JRS2-80/Z
JRS2-135/Z
JRS2-150/Z
 
JRS2-180/F
JRS2-400/F
JRS2-630F
 

1.Application

JRS(3UA)2 thermal relay is suitable for AC 50/60Hz, voltage up to 660V and current up to 630A,general AC motor of long or discontinuous long operation, used as overload protection and hasthe functions of breaking phase protection, temperature compensation, and trip indication. Itcan automatically and manually get back. It can be fixed with contactor CJX1 together, also beindependtly fixed. The product conforms to IEC60947-4-1 stardand.

2. Motion Characteristic: Three-phase Balance Motion Time
No Times of the setting current Motion time Start condition Ambient temperature
1 1.05 >2h Cold state 20±5oC
2 1.2 <2h Heat state(Following the No.1 test)
3 1.5 <4min
4 7.2 10A 2s< Tp≤10s ≤63A Cold state
10 4s< Tp≤10s >63A

3. Phase-losing Motion Characteristic
No Times of the setting current Motion time Start condition Ambienttemperature
Any two phases Another phase
1 1.0 0.9 >2h Cold state 20±5oC
2 1.15 0 <2h Heat state(Following the No.1 test)

4. Specification
Type Number Setting range(A) For contactor Type Number Setting range(A) For contactor
JRS2-12.5/Z
(3UA50)
0A 0.1~0.16 3TB40
3TF40
3TB41
3TF41
JRS2-25/Z
(3UA52)
0A 0.1~0.16 3TB40
3TF40
3TB41
3TF41
0C 0.16~0.25 0C 0.16~0.25
0E 0.25~0.4 0E 0.25~0.4
0G 0.4~0.63 0G 0.4~0.63
0J 0.63~1 0J 0.63~1
0K 0.8~1.25 0K 0.8~1.25
1A 1~1.6 1A 1~1.6
1B 1.25~2 1B 1.25~2
1C 1.6~2.5 1C 1.6~2.5
1D 2~3.2 1D 2~3.2
1E 2.5~4 1E 2.5~4
1F 3.2~5 1F 3.2~5
1G 4~6.3 1G 4~6.3
1H 5~8 1H 5~8
1J 6.3~10 1J 6.3~10
1K 8~12.5 1K 8~12.5
2S 10~14.5 2A 10~16
2B 12.5~20
2C 16~25
Type Number Setting range(A) For contactor Type Number Setting range(A) For contactor
JRS2-32/Z
(3UA50)
1G 4~6.3 3TB44 JRS2-63/F
(3UA59)
0K 0.8~1.25 3TB40-48
3TF30-48
1J 6.3~10 1A 1~1.6
2A 10~16 1B 1.25~2
2B 12.5~20 1C 1.6~2.5
2C 16~25 1D 2~3.2
2D 20~32 1E 2.5~4
2Q 25~36 1F 3.2~5
JRS2-45/Z
(3UA55)
0A 0.1~0.16 3TF44
3TF45
1G 4~6.3
0C 0.16~0.25 1H 5~8
0E 0.25~0.4 1J 6.3~10
0G 0.4~0.63 1K 8~12.5
0J 0.63~1 2A 10~16
0K 0.8~1.25 2B 12.5~20
1A 1~1.6 2C 16~25
1B 1.25~2 2D 20~32
1C 1.6~2.5 2E 25~40
1D 2~3.2 2M 32~45
1E 2.5~4 2T 40~57
1F 3.2~5 2P 50~63
1G 4~6.3 JRS2-135
(3UA60)
2H 55~80 3TF40-50
3TF30-48
1H 5~8 2W 63~90
1J 6.3~10 2X 80~110
1K 8~12.5 3H 90~120
2A 10~16 3J 110~135
2B 12.5~20 JRS2-150
(3UA61)
2H 55~80 3TF51
2C 16~25 2W 63~90
2D 20~32 2X 80~110
2Q 25~36 3H 90~120
2R 32~40 3J 110~135
8M 36~45 3K 120~150
1G 4~6.3 3TF46
3TF47
3TF48
JRS2-180/F
(3UA62)
2H 55~80 3TF51
3TB52
3TF50
3TF52
JRS2-80/Z
(3UA58)
8A 11~17 2W 63~90
2B 12.5~20 2X 80~110
2C 16~25 3H 90~120
2D 20~32 3J 110~135
2E 25~40 3K 120~150
2F 32~50 3L 135~160
2T 40~57 3M 150~180
2P 50~63 JRS2-400
(3UA66)
2K 80~125 3TF54
3TB56
2V 57~70 3B 125~200
2U 63~80 3C 160~250
8W 70~88 3D 200~320
JRS2-63/F
(3UA59)
0A 0.1~0.16 3TF40-48
3TF30-48
3E 250~400
0C 0.16~0.25 JRS2-630
(3UA66)
3F 3TF56
3TB57
0E 0.25~0.4 3G
0G 0.4~0.63
0J 0.63~1

5. Outline and Mounting Dimension
Type JRS2-400 JRS2-630
a 50 52
b 146 156
c 70 71
Φ 11 11
e 171 186
f 25×4 30×5

6. Accessories
Pic
Description JRS2 mounting base JRS2 mounting base JRS2 mounting base Terminal block box
Application Assembled withJRS2-12.5/Z to form a complete set Assembled withJRS2-80/Z to form a complete set Assembled withJRS2-45/Z to form a complete set Assembled withJRS2-135/Z to form a complete set